Monitoring the LNF Scanning LAB Conditioning System

Operations on the Scanning LAB Conditioning System:

Date Action Operator
19 June 2008 Replacement of the air conditioner external fan and dust filters.
Installation of water evacuation pump.
Goal temperature and humidity set to (21+-0.5)C and (60+-5)%.
Sebastianelli
23 Jun 2008 External temperature and humidity measurements made available on meteo log file.
Denni
24 Jun 2008 10h00 Goal temperature and humidity set to (21+-0.2)C and (60+-1)%.
Denni and Sebastianelli
25 Jun 2008 11h00 External air vent closed.
Denni
26 Jun 2008 15h00 Two false ceiling panels taken off.
Wind speed measurements made available on meteo log file.
Sebastianelli and Denni
26 Jun 2008 LNF water supply failure. Registered air conditioner moistener alarm.
28 Jun 2008 17h00 Meteo monitoring software failure: no data registered on meteo.log until 30 Jun 8h48.
30 Jun 2008 13h00 Small moistener turned on.
Denni and Paniccia
1 Jul 2008 15h15 False ceiling panels taken off on June 26th mounted back.
Denni and Paniccia
1 Jul 2008 16h00 Small moistener placed on the floor in front of air conditioner and increased moist emission rate.
Denni and Paniccia
2 Jul 2008 10h15 Water condensed beneath air conditioner: small moistener moved away from air conditioner.
Deactivated air conditioner moistening function.
Increased small moistener emission rate.
Sebastianelli and Paniccia
2 Jul 2008 16h30 Still water condensed beneath air conditioner (again).
Increased small moistener emission rate.
Paniccia
3 Jul 2008 11h00 Still water condensed beneath air conditioner: requested Sebastianelli intervention.
Small moistener run out of water: refilled.
Small moistener moved near the door.
Paniccia
3 Jul 2008 12h00 Server and PC MIC2 powered up. Paniccia
3 Jul 2008 15h00 Air conditioner checked. Sebastianelli
3 Jul 2008 15h30 Goal temperature set to (19+-0.5)C. Sebastianelli and Paniccia
3 Jul 2008 16h30 Four false ceiling panels taken off. Sebastianelli and Denni
4 Jul 2008 10h30 Insulated copper tubes to prevent water condensation from air conditioner. Sebastianelli
4 Jul 2008 ~11h30 Meteo monitoring software failure: no data registered on meteo.log until 7 Jul 11h15.
11 Jul 2008 19h00 Small moistener refilled (Running out of water foreseen on 12 Jul night time). Paniccia
12 Jul 2008 ~2h00 Air conditioner failure.
14 Jul 2008 10h30 Server and PC MIC2 turned off. Paniccia
14 Jul 2008 11h00 Air conditioner restarted: the air filter was dirty. Sebastianelli and Denni
14 Jul 2008 14h00 Small moistener refilled and turned on. Server and PC MIC2 turned on. Paniccia
16 Jul 2008 ~0h00 Air conditioner failure: low pressure in compressor 1.
16 Jul 2008 10h40 Air conditioner restarted. Sebastianelli
17 Jul 2008 ~0h00 Air conditioner failure: low pressure in compressor 1.
17 Jul 2008 11h00 Air conditioner turned off: waiting for Sebastianelli intervention. Small moistener, Server and PC MIC2 turned off. Paniccia
5 Aug 2008 12h00 Compressor 1 checked out: the expansion valve has to be replaced. Intervention foreseen NET August 18th 2008. Sebastianelli
6 Aug 2008 14h40 PC meteo monitoring turned off because of lab re-arrangement. Paniccia
7 Aug 2008 10h30 Meteo monitoring restarted. Denni
29 Aug 2008 Meteo monitoring turned off in view of LNF power cut foreseen tomorrow. Denni
2 Sep 2008 9h00 Meteo monitoring restarted. Denni
2 Sep 2008 16h00 Air conditioner system repaired: expansion valve replaced. Goal temperature set to (20+-1)C; moistening excluded. Small moistener still off. Sebastianelli
3 Sep 2008 10h30 Server and PC MIC2 turned on. Paniccia
3 Sep 2008 11h50 Air conditioner goal temperature set to (22+-1)C. Paniccia and Denni
4 Sep 2008 16h00 Small moistener on. Paniccia
5 Sep 2008 9h00 Small moistener emission rate lowered. Paniccia
5 Sep 2008 18h00 Server, PC MIC2 and small moistener turned off (Operator out of lab till Sep 15). Paniccia
15 Sep 2008 10h12 Server, PC MIC2 and small moistener turned on (Operator back to work). Paniccia
18 Sep 2008 14h15 Goal temperature set to (21+-1)C; Paniccia
18 Sep 2008 16h30 Goal temperature set to (21.5+-1)C; Paniccia
30 Sep 2008 10h00 Small moistener turned off. Air conditioner system moistening function activated. SetPoint Temperature: (21.0+-1.2)C; Humidity: (65+-6)% Paniccia
30 Sep 2008 16h38 Maybe the water tap was closed... ..now should be open... ..I hope! (1 Oct 2008: No, I've just excluded the water filter!) Paniccia
1 Oct 2008 18h15 SetPoint Humidity: (70+-6)% Paniccia
2 Oct 2008 14h30 Air conditioner setting checked: For the new parameters to be acquired the system has to be restarted. The black tap should have the red sign toward the A for the water to be filtered before entering the machine. Sebastianelli (Paniccia)
9-10 Oct 2008 Air conditioner moistening failure, temperature control still working. Paniccia
13 Oct 2008 15h30 Air conditioner repaired: water drain electrovalve replaced. Sebastianelli

Last modified: Mon Oct 13 17:53:49 CEST 2008